UV & TRIPLE IR Flame Detector
♦ Can Identifies Multi-Spectral Sensitivity of Fire through the Utilization of UV & IR Detectors
♦ 30 Metres of Clear Line of Sight Visual Range.
♦ Triple Spectrum Design - for Long Distance Detection & Excellent False Alarm Immunity
♦ Sensitivity Selection - To ensure no zone cross over detection.
♦ High Sensitivity - combined with fast response time to ensure rapid & accurate flame detection.
♦ 2 Nos. Potential Free Relay Output with Audio Visual Hooter Alarm.
♦ Isolated 4 - 20 mA DC Output (Stepped)
♦ Multi-drop RS485 Modbus RTU Communication for SCADA / DCS Connectivity
♦ Micro Controller based Highly Accurate, Reliable and High Performance based Technology.
♦ Fast and Reliable Output by using Electrochemical / Pellister / NDIR Sensors.
♦ Opmized design for detecon of smallest leak of HCL Gas
♦ Digital seven segment LED or LCD Display for Monitoring of GAS Concentraon
♦ Front Capacitive Finger Touch Key Operation
♦ 3 level Password Protecon for Configuraon and Calibraon.
♦ Isolated 4 - 20 mA Process Value Re-Transmission Output
♦ Modbus RTU Muldrop RS485 / RF-Wireless / Wi-Fi / Bluetooth Communicaon Port
♦ Process Parameter High and Low LED Status Indicaon with Audible Buzzer / Flasher for Limit Violaon
♦ Long Life Sensor - 2 / 5 Years
| Measuring Principle | UV Band (185 nm to 260 nm) Three IR Band (3000 to 5000 nm) |
| Response Time | Typically less than 5 Second (Depending on Flame Size & Sensitivity) |
| Field of View | 90° Horizontal & Vertical |
| Adjustable Time Delay | Up to 30 Second |
| 4 - 20 mA Output | Stepped Output Fault: 1 mA Normal: 4 mA Fire Detect: 20 mA |
| - | |
| Relay | 2 Nos. Potential Free Relay for Fail Safe, Fire Detection & Auxilary Output |
| Communication | RS485 Modbus Multidrop RTU |
| Operating Temperature | -20 to 85°C |
| Humidity | < 95% Non Condensing |
| Environment Protection | IP66 & IP68 |
| Enclosure | Cast Aluminium Alloy LM-6 Construction |
| Mounting | Wall Mount / Pipe Mount |
| Power Supply | 24 V DC |